EPS and thermal insulation
Choosing EPS beneath a terrace above a heated room
At a glance
A terrace above a heated room is at the same time a roof and a usable surface. EPS can reduce heat losses, but it must match the waterproofing build-up and the loads from the surfacing. With boards on pedestals, local contact pressures matter. With heavy layers, creep also matters. Selection begins with the cross-section of the entire terrace. In a traditional terrace, the water-protection layer is located above the thermal insulation. EPS works beneath a covering that is to protect it from rainwater. In such a build-up, suitable roof-and-floor boards can be considered. Their suitability depends on the documentation for the solution, the loads and how the other layers are executed. The name terrace does not mean one single, always identical cross-section.

First establish the position of the waterproofing
In an inverted roof build-up, the insulation lies above the waterproofing and may come into contact with water. This does not make ordinary roof EPS the right material. A variant intended for such conditions or suitably selected XPS is required. The requirements for the two build-ups must not be mixed. The position of the thermal insulation layer also affects the calculations and the method of drainage.
How does the surface transfer load?
Tiles on a suitably designed base, boards on pedestals and planks on battens load the insulation in different ways. A pedestal transfers force onto a limited area. Its size matters just as much as the weight of the surface. People, furniture and planned equipment must also be taken into account. A heavy planter at the edge is not the same case as an evenly distributed layer.
Protective pads do not have to perform the function of structural load distribution. Their task may primarily be to protect the covering. The design should indicate how the force passes through all layers to the floor slab. One should not assume on one’s own that a wider pedestal foot will solve every problem. The conditions of use of the surface and data on the insulation are needed.
Why is CS(10) not enough?
CS(10) describes the stress at a specified, large deformation in a compression test. It is not the permissible pressure during many years of terrace use. A permanent weight can cause further deformation of the material over time. Data on creep, a CC declaration or other relevant manufacturer data are therefore needed. The designer takes them into account together with the requirements for the entire system.
Slight uneven settlement may be significant for a rigid surface, the slope or the tightness of a detail. The selection should therefore not end with the statement that the board is hard. Density and assessment by hand do not replace declared properties. It is also worth establishing whether a future change of equipment will require a new assessment. A terrace with light furniture may in time receive completely different loads.
Thickness must be tied to the threshold
The thermal resistance of the EPS layer depends on its thickness and its lambda value. For example, 16 cm at λ = 0.032 gives R = 5.0 m²K/W. This is the result for the insulation alone, not the Uc value of the terrace. The whole assembly requires a separate calculation. The available space beneath the surface covering must be taken into account, as well as the thinnest sections if the fall is created with tapered boards.
The door threshold often limits the height of the layers. Determining this height too late can force an unfavourable reduction in the thickness of the thermal insulation or a problematic upstand of the waterproofing. The door, the drainage and the floor inside must be drawn at the same time. Selecting EPS with a better lambda value alone will not fix a detail in which no space has been allowed for a watertight connection and water drainage.
Waterproofing and drainage are separate tasks
EPS does not replace the water-protection layer. The connections at walls, balustrades and drains must be watertight. A surface covering with joints or open gaps can let water through to the lower layers. A path for its drainage must be allowed for. The arrangement of falls should relate to the surface that drains the water, not only to the visible top of the terrace.
The covering, adhesives and separating layers must be compatible with EPS. With roofing felt, the technology that protects the insulation from the welding temperature is important. With a membrane, a specific separating layer may be required. Balustrades and other fixings must be designed without accidentally piercing the seals. Access to the drains must be maintained even after the boards have been laid and the equipment has been positioned.
What should be recorded in the order and at acceptance?
It is worth stating the intended use, lambda value, thickness and required mechanical properties in the order. Data enabling an assessment of performance over time are also needed. On acceptance, the conformity of the material, the support of the boards and the execution of the details before they are covered are checked. Conformity of the pack thickness with the order alone does not confirm that the layer under the supports is correct.
Well-known EPS manufacturers include Swisspor, Paneltech, Arsanit and Austrotherm. Their documentation should be consulted for specific solutions suitable for the project. A terrace requires the coordination of thermal insulation, waterproofing, the surface and the structure. A good choice of EPS is part of that decision, not a substitute for checking loads and the details at doors and edges.